<?xml version="1.0" encoding="utf-8"?>
<project xmlns="http://www.plcopen.org/xml/tc6_0200">
  <fileHeader companyName="Anonymous" productName="Benchmark Suite" productVersion="1.0" creationDateTime="2026-09-02T00:00:00" />
  <contentHeader name="g_dead_bus_close_check_clean"><coordinateInfo><fbd><scaling x="1" y="1" /></fbd><ld><scaling x="1" y="1" /></ld><sfc><scaling x="1" y="1" /></sfc></coordinateInfo></contentHeader>
  <types><dataTypes /><pous><pou name="g_dead_bus_close_check_clean" pouType="program">
    <interface><inputVars><variable name="close_request"><type><BOOL /></type></variable><variable name="bus_live"><type><BOOL /></type></variable><variable name="sync_check_ok"><type><BOOL /></type></variable><variable name="maint"><type><BOOL /></type></variable></inputVars><outputVars><variable name="breaker_close"><type><BOOL /></type></variable></outputVars></interface>
    <body><LD>
      <leftPowerRail localId="0"><position x="0" y="0" /><connectionPointOut formalParameter="none" /></leftPowerRail>
      <contact localId="3" negated="false" storage="none" edge="none"><position x="20" y="10" /><connectionPointIn><connection refLocalId="0" /></connectionPointIn><connectionPointOut /><variable>close_request</variable></contact><contact localId="4" negated="true" storage="none" edge="none"><position x="40" y="10" /><connectionPointIn><connection refLocalId="3" /></connectionPointIn><connectionPointOut /><variable>bus_live</variable></contact><contact localId="5" negated="false" storage="none" edge="none"><position x="20" y="30" /><connectionPointIn><connection refLocalId="0" /></connectionPointIn><connectionPointOut /><variable>close_request</variable></contact><contact localId="6" negated="false" storage="none" edge="none"><position x="40" y="30" /><connectionPointIn><connection refLocalId="5" /></connectionPointIn><connectionPointOut /><variable>sync_check_ok</variable></contact><coil localId="7" negated="false" storage="none"><position x="80" y="10" /><connectionPointIn><connection refLocalId="4" /><connection refLocalId="6" /></connectionPointIn><connectionPointOut /><variable>breaker_close</variable></coil>
      <rightPowerRail localId="2147483646"><position x="400" y="0" /><connectionPointIn /></rightPowerRail>
    </LD></body>
  </pou></pous></types>
  <instances><configurations><configuration name="Config0"><resource name="Res0"><task name="tcyclic" interval="T#10ms" priority="0"><pouInstance name="inst0" typeName="g_dead_bus_close_check_clean" /></task></resource></configuration></configurations></instances>
</project>