Fail-Safe Motor Latch

suite id g_failsafe_motor_latch
domain motor_control
language LD-graphical
difficulty easy
validation status validated
origin lessons-electric-circuits
license Design Science License

Lessons In Electric Circuits, Volume IV - Digital, Chapter 6 (Fail-safe design), by Tony R. Kuphaldt

What is proved

From benchmarks/motor_control/g_failsafe_motor_latch/props.yaml. What each kind claims, and what it becomes on either route, is on The properties we prove.

id kind claim requirement
P1 invariant THERMAL_OVERLOAD_NC || !MOTOR_RUN Fire Hazard: The motor coil must instantly de-energize if the hardware thermal overload relay physically trips (opening the NC circuit).

Variants

file expected verdict violates method
failsafe_motor_latch.xml SAFE none expert

Files

file what it is size sha256
NOTES.md notes 1.4 KB 7454246fc95e
benchmark.yml benchmark metadata 0.8 KB 60e87b1bfdeb
failsafe_motor_latch.xml ladder program, PLCopen XML 3.0 KB 3d16843f5bb5
props.yaml property file 0.3 KB c3fb22b09d1e

Structured text, derived

Read off the ladder graph by runner/ld_to_st.py: every rung's contacts and coils rewritten as IEC 61131-3 assignments, in the same series/parallel logic the PLCopen XML encodes. This is a reading aid, not a second source of expected verdicts; ESBMC verifies the ladder program shown above, never this rendering.

PROGRAM main
VAR
    START : BOOL;
    THERMAL_OVERLOAD_NC : BOOL;
    STOP_NC : BOOL;
    MOTOR_RUN : BOOL;
END_VAR


MOTOR_RUN := (((START OR MOTOR_RUN) AND THERMAL_OVERLOAD_NC) AND STOP_NC);

END_PROGRAM

Recorded runs

A task can carry two routes. ld is ESBMC's ladder front end reading the program directly. via C is the same solver reached through Beremiz and MatIEC, which is the only route that reaches ST, IL, FBD and SFC; see How ESBMC-PLC works.

  • g_failsafe_motor_latch__failsafe_motor_latch (props.yaml, expected SAFE): v8.4 SAFE