Every bomb in Parts 2 and 3 was written for this suite. That is a weakness, and it is worth saying plainly: an attack you invented yourself is an attack you already knew how to catch. This part uses eight pairs somebody else published.

The plant

A water tank with two motorized valves. MV1 fills, MV2 drains, a level transmitter reports the contents, and the controller reads that level, subtracts a calibration offset, and opens one valve or the other depending on which threshold the corrected value has crossed.

real_value := IN1 - 5;
if real_value <= IN_TLB2 then OUT_MV2 := FALSE; OUT_MV1 := TRUE;  end_if;
if real_value >= IN_TLB1 then OUT_MV2 := TRUE;  OUT_MV1 := FALSE; end_if;

Fill below the low threshold, drain above the high one. A stop_cycle block latches the run state, and the ladder in program0 wires the pieces together.

The property is not about valves

benchmarks/water_treatment/g_tank_assignment/props.yaml
format_version: "0.1"
properties:
  - id: P1
    kind: termination
    justification: "Every PLC scan cycle must complete (no non-terminating loop). The malicious variant injects a Govil et al. LLB: a while-loop whose counter is never advanced, gated on a specific sensor value, so a scan hangs and the controller stops responding. Program context: Direct assignment variant of the tank controller."

The claim being defended is that every scan finishes. Nothing in it mentions a valve, a level or a threshold, which looks like a strange thing to verify until you see what the attacks do.

That file is documentation rather than input. Termination is the one property kind ESBMC does not take through --ld-props, so the recorded commands in this part omit the flag and let --ld-scan-watchdog --ld-scan-budget 8 carry the check. The YAML records what the suite claims; the watchdog is what tests it.

A PLC runs its program in a loop: read inputs, execute, write outputs, repeat. Outputs change only at the end of a scan. A program that never reaches the end of a scan therefore never writes an output again, and the valves hold whatever position they had when the scan began. The plant does not stop. It freezes, with the last command still in force, and the operator's next command never arrives.

This is denial of control, the third payload class in Govil, Agrawal and Tippenhauer's taxonomy, and it is the class no assertion about a variable's value can catch. The variable never gets a wrong value. It stops getting values at all.

Where the programs come from

Antonio Iacobelli, Lorenzo Rinieri, Andrea Melis, Amir Al Sadi, Marco Prandini and Franco Callegati, Detection of Ladder Logic Bombs in PLC Control Programs: an Architecture based on Formal Verification, IEEE 7th International Conference on Industrial Cyber-Physical Systems (ICPS) 2024, pages 1–7. DOI 10.1109/ICPS59941.2024.10639995. Dataset: UniboSecurityResearch/PLC-LD-dataset.

The dataset holds legitimate and malicious versions of the same tank controller, in PLCopen XML, as pairs. Eight pairs are in this catalog. Each pair differs in one edit, the legitimate half is expected to verify and the malicious half is expected to fail, and both expectations come from the dataset's own labels rather than from anything ESBMC said.

That last point is what makes this part worth more than Part 2. The expected verdicts were fixed by other people, for their own paper, before this suite existed.

Eight edits, two techniques

Reading the diffs, the eight attacks fall into two groups.

Four of them inject a loop into a function block body that is already there. The block keeps doing its job, and a few lines are appended that do something else on one input value.

Four of them replace a standard block with a user-defined one whose name differs by two characters. EQ becomes EQ_0. The replacement reimplements the comparison correctly, so the ladder behaves normally, and carries the bomb underneath.

benchmark technique trigger loop
g_tank_assignment injected loop real_value = 25 while i<3, i set to 1
g_tank_valves injected loop real_value = 25 while i<15, i never set
g_tank_substitution_coil injected loop IN1 = 46 while i<4, i never set
g_tank_value_filtering injected loop, block removed real_value = 25 while i<15, i never set
g_tank_start_eq EQ → EQ_0 IN1 = 12 while i<4, i never set
g_tank_start_le LE → LE_0 IN1 = 12 while i<4, i never set
g_tank_stop_ge GE → GE_0 IN1 = 12 while i<4, i never set
g_tank_sub_function SUB → SUB_0 IN1 = 25 while i<4, i never set

Seven of the eight loops omit the increment entirely. One sets the counter to a value that still fails the test, which is the only one that would survive a reader who checks whether the variable is assigned at all.

The rest of this part takes one attack from each group, then the two that do something the others do not.