A lockout that lets go

A gas burner lights in a fixed order, and EN 298 fixes it: run the fan long enough to sweep the chamber, open the pilot, prove the flame, and only then admit main gas. Get the order wrong and you are igniting a chamber that has been filling with fuel.

The second requirement is about what happens after a failure. A burner that fails to light must go to lockout, and lockout is non-volatile: it needs somebody to walk up and press reset. A controller that retries on its own is doing unsupervised ignition attempts on a chamber that has already proved it will not light.

The rungs

CallForHeatFanLockoutFlameFailResetBtnLockoutCallForHeatPurgeDoneLockoutPilotCallForHeatPurgeDoneFlameProvenLockoutMainValve

Lockout := (Lockout OR FlameFail) AND NOT ResetBtn, Pilot := CallForHeat AND PurgeDone AND NOT Lockout, MainValve := CallForHeat AND PurgeDone AND FlameProven AND NOT Lockout.

file what it is size sha256
program.xml ladder program, PLCopen XML 4.8 KB 8d5a0314b1d6
self_clearing.xml ladder program, PLCopen XML 4.6 KB e9618b8c237c
props.yaml property file 0.2 KB 0d8c0bb4baa6
lockout_check.props.yaml property file 0.4 KB d95e72df20cc

The property everyone writes

benchmarks/hvac/g_burner_purge/props.yaml
format_version: "0.1"
properties:
  - id: P1
    kind: invariant
    expression: "!MainValve || (PurgeDone && FlameProven)"
    justification: "EN 298 light-off order: the main gas valve opens only after the purge has completed and the flame is proven."

Recorded 2026-09-04T23:40:46Z. Every build ran the same command.

cp benchmarks/hvac/g_burner_purge/program.xml benchmarks/hvac/g_burner_purge/program.ld
esbmc benchmarks/hvac/g_burner_purge/program.ld --ld-props benchmarks/hvac/g_burner_purge/props.yaml --k-induction --ld-scan-watchdog --ld-scan-budget 8 --timeout 20s

Recorded 2026-09-04T23:40:46Z.

cp benchmarks/hvac/g_burner_purge/program.xml benchmarks/hvac/g_burner_purge/program.ld
esbmc benchmarks/hvac/g_burner_purge/program.ld --ld-props benchmarks/hvac/g_burner_purge/props.yaml --k-induction --ld-scan-watchdog --ld-scan-budget 8 --timeout 20s
build ESBMC verdict expected outcome ingestion gate cpu
v8.4 8.4.0 SAFE SAFE correct pass 0.018 s

v8.4 found its solution by the inductive step (k = 2).

What the front end encoded. The scan body as the solver receives it, branch guards kept. An assignment-only view hides the guards and makes a guarded accumulator read as a constant.

     1: IF !1 THEN GOTO 2
        ASSIGN CallForHeat=NONDET(_Bool);
        ASSIGN PurgeDone=NONDET(_Bool);
        ASSIGN FlameProven=NONDET(_Bool);
        ASSIGN FlameFail=NONDET(_Bool);
        ASSIGN ResetBtn=NONDET(_Bool);
        ASSIGN MainValve=1 && CallForHeat && PurgeDone && FlameProven && !Lockout;
        ASSIGN Pilot=1 && CallForHeat && PurgeDone && !Lockout;
        ASSIGN Lockout=1 && Lockout && !ResetBtn;
        ASSIGN Lockout=1 && FlameFail && !ResetBtn;
        ASSIGN Fan=1 && CallForHeat;
        GOTO 1
     2:

That is the light-off order, and it is the property a commissioning engineer would ask for. It says nothing whatever about lockout, so a controller with no lockout at all satisfies it.

Predict the verdict

In this variant the lockout follows the flame-fault contact and clears itself. Does the light-off order still hold?

Answer
build verdict expected ingestion gate
v8.4 SAFE SAFE pass

The discriminator

benchmarks/hvac/g_burner_purge/lockout_check.props.yaml
# Discriminator, not a safety requirement. A burner lockout is non-volatile and needs a
# manual reset, so it outlives the flame fault that caused it. A lockout that clears
# itself proves this property and lets the burner retry unattended.
format_version: "0.1"
properties:
  - id: P1
    kind: invariant
    expression: "!Lockout || FlameFail"
    justification: "Lockout holds only while the flame fault is present. A latching lockout must refute this."

Recorded 2026-08-28T18:37:07Z. Every build ran the same command.

cp benchmarks/hvac/g_burner_purge/program.xml benchmarks/hvac/g_burner_purge/program.ld
esbmc benchmarks/hvac/g_burner_purge/program.ld --ld-props benchmarks/hvac/g_burner_purge/lockout_check.props.yaml --k-induction --ld-scan-watchdog --ld-scan-budget 8 --timeout 30s

Recorded 2026-08-28T18:37:07Z.

cp benchmarks/hvac/g_burner_purge/program.xml benchmarks/hvac/g_burner_purge/program.ld
esbmc benchmarks/hvac/g_burner_purge/program.ld --ld-props benchmarks/hvac/g_burner_purge/lockout_check.props.yaml --k-induction --ld-scan-watchdog --ld-scan-budget 8 --timeout 30s
build ESBMC verdict expected outcome ingestion gate cpu
master 8.4.0 0064c4ac VIOLATION VIOLATION correct pass 0.015 s

What the front end encoded. The scan body as the solver receives it, branch guards kept. An assignment-only view hides the guards and makes a guarded accumulator read as a constant.

     1: IF !1 THEN GOTO 25
        ASSIGN CallForHeat=NONDET(_Bool);
        ASSIGN PurgeDone=NONDET(_Bool);
        ASSIGN FlameProven=NONDET(_Bool);
        ASSIGN FlameFail=NONDET(_Bool);
        ASSIGN ResetBtn=NONDET(_Bool);
        ASSIGN Lockout__prev=1 && Lockout;
        IF !1 THEN GOTO 2
        ASSIGN pf13=0;
     2: IF !(1 && CallForHeat) THEN GOTO 3
        ASSIGN pf13=1;
     3: IF !1 THEN GOTO 4
        ASSIGN pf14=0;
     4: IF !(1 && pf13 && PurgeDone) THEN GOTO 5
        ASSIGN pf14=1;
     5: IF !1 THEN GOTO 6
        ASSIGN pf15=0;
     6: IF !(1 && pf14 && FlameProven) THEN GOTO 7
        ASSIGN pf15=1;
     7: IF !1 THEN GOTO 8
        ASSIGN pf16=0;
     8: IF !(1 && pf15 && !Lockout__prev) THEN GOTO 9
        ASSIGN pf16=1;
     9: ASSIGN MainValve=1 && pf16;
        IF !1 THEN GOTO 10
        ASSIGN pf9=0;
    10: IF !(1 && CallForHeat) THEN GOTO 11
        ASSIGN pf9=1;
    11: IF !1 THEN GOTO 12
        ASSIGN pf10=0;
    12: IF !(1 && pf9 && PurgeDone) THEN GOTO 13
        ASSIGN pf10=1;
    13: IF !1 THEN GOTO 14
        ASSIGN pf11=0;
    14: IF !(1 && pf10 && !Lockout__prev) THEN GOTO 15
        ASSIGN pf11=1;
    15: ASSIGN Pilot=1 && pf11;
        IF !1 THEN GOTO 16
        ASSIGN pf6=0;
    16: IF !(1 && FlameFail) THEN GOTO 17
        ASSIGN pf6=1;
    17: IF !1 THEN GOTO 18
        ASSIGN pf5=0;
    18: IF !(1 && Lockout__prev) THEN GOTO 19
        ASSIGN pf5=1;
    19: IF !1 THEN GOTO 20
        ASSIGN pf7=0;
    20: IF !(1 && pf6 && !ResetBtn) THEN GOTO 21
        ASSIGN pf7=1;
    21: IF !(1 && pf5 && !ResetBtn) THEN GOTO 22
        ASSIGN pf7=1;
    22: ASSIGN Lockout=1 && pf7;
        IF !1 THEN GOTO 23
        ASSIGN pf3=0;
    23: IF !(1 && CallForHeat) THEN GOTO 24
        ASSIGN pf3=1;
    24: ASSIGN Fan=1 && pf3;
        GOTO 1
    25:

Counterexample. ESBMC's own output. A trace long enough to need it is elided in the middle, and the omission is marked and counted where it happens.

State 1  thread 0
----------------------------------------------------
  FlameFail = 1

State 2  thread 0
----------------------------------------------------
  ResetBtn = 0

State 3  thread 0
----------------------------------------------------
  Lockout = 1

State 5  thread 0
----------------------------------------------------
  FlameFail = 0

State 6  thread 0
----------------------------------------------------
  ResetBtn = 0

State 7  thread 0
----------------------------------------------------
  Lockout__prev = 1

State 8  thread 0
----------------------------------------------------
  Lockout = 1

State 9 file benchmarks/hvac/g_burner_purge/program.ld thread 0
----------------------------------------------------
Violated property:
  file benchmarks/hvac/g_burner_purge/program.ld
  P1
  !Lockout || FlameFail


** Results:
  NOT CHECKED  [global.assertion.1]  line 0  unwinding assertion loop 1
benchmarks/hvac/g_burner_purge/program.ld
  FAILED       [global.assertion.2]  line 0  P1

** 1 of 2 properties failed, 1 not checked
   (this mode stops at the first violation; use --multi-property for a verdict on every property)

Refuted, which is the right answer: a latching lockout outlives the fault that set it. A front end that flattened the two branches into Lockout would prove this instead, soundly, about a lockout that is a plain copy of FlameFail AND NOT ResetBtn.

Recorded 2026-08-28T18:37:07Z. Every build ran the same command.

cp benchmarks/hvac/g_burner_purge/self_clearing.xml benchmarks/hvac/g_burner_purge/self_clearing.ld
esbmc benchmarks/hvac/g_burner_purge/self_clearing.ld --ld-props benchmarks/hvac/g_burner_purge/lockout_check.props.yaml --k-induction --ld-scan-watchdog --ld-scan-budget 8 --timeout 30s

Recorded 2026-08-28T18:37:07Z.

cp benchmarks/hvac/g_burner_purge/self_clearing.xml benchmarks/hvac/g_burner_purge/self_clearing.ld
esbmc benchmarks/hvac/g_burner_purge/self_clearing.ld --ld-props benchmarks/hvac/g_burner_purge/lockout_check.props.yaml --k-induction --ld-scan-watchdog --ld-scan-budget 8 --timeout 30s
build ESBMC verdict expected outcome ingestion gate cpu
master 8.4.0 0064c4ac SAFE SAFE correct pass 0.017 s

master found its solution by the inductive step (k = 2).

What the front end encoded. The scan body as the solver receives it, branch guards kept. An assignment-only view hides the guards and makes a guarded accumulator read as a constant.

     1: IF !1 THEN GOTO 22
        ASSIGN CallForHeat=NONDET(_Bool);
        ASSIGN PurgeDone=NONDET(_Bool);
        ASSIGN FlameProven=NONDET(_Bool);
        ASSIGN FlameFail=NONDET(_Bool);
        ASSIGN ResetBtn=NONDET(_Bool);
        ASSIGN Lockout__prev=1 && Lockout;
        IF !1 THEN GOTO 2
        ASSIGN pf12=0;
     2: IF !(1 && CallForHeat) THEN GOTO 3
        ASSIGN pf12=1;
     3: IF !1 THEN GOTO 4
        ASSIGN pf13=0;
     4: IF !(1 && pf12 && PurgeDone) THEN GOTO 5
        ASSIGN pf13=1;
     5: IF !1 THEN GOTO 6
        ASSIGN pf14=0;
     6: IF !(1 && pf13 && FlameProven) THEN GOTO 7
        ASSIGN pf14=1;
     7: IF !1 THEN GOTO 8
        ASSIGN pf15=0;
     8: IF !(1 && pf14 && !Lockout__prev) THEN GOTO 9
        ASSIGN pf15=1;
     9: ASSIGN MainValve=1 && pf15;
        IF !1 THEN GOTO 10
        ASSIGN pf5=0;
    10: IF !(1 && FlameFail) THEN GOTO 11
        ASSIGN pf5=1;
    11: IF !1 THEN GOTO 12
        ASSIGN pf6=0;
    12: IF !(1 && pf5 && !ResetBtn) THEN GOTO 13
        ASSIGN pf6=1;
    13: ASSIGN Lockout=1 && pf6;
        IF !1 THEN GOTO 14
        ASSIGN pf3=0;
    14: IF !(1 && CallForHeat) THEN GOTO 15
        ASSIGN pf3=1;
    15: ASSIGN Fan=1 && pf3;
        IF !1 THEN GOTO 16
        ASSIGN pf8=0;
    16: IF !(1 && CallForHeat) THEN GOTO 17
        ASSIGN pf8=1;
    17: IF !1 THEN GOTO 18
        ASSIGN pf9=0;
    18: IF !(1 && pf8 && PurgeDone) THEN GOTO 19
        ASSIGN pf9=1;
    19: IF !1 THEN GOTO 20
        ASSIGN pf10=0;
    20: IF !(1 && pf9 && !Lockout__prev) THEN GOTO 21
        ASSIGN pf10=1;
    21: ASSIGN Pilot=1 && pf10;
        GOTO 1
    22:

Two lockouts, one verdict

Put the four runs together. The property that was actually shipped, the light-off order, says SAFE for the burner that latches and SAFE for the burner that does not. A results table built from it would report a working lockout in both rows.

The pattern is worth naming because it generalizes past this benchmark. Wherever a requirement reduces to "this memory outlives its cause", the check for it is a refutation, and both a program without the memory and a front end that quietly drops it will pass anything weaker.