Stop-on-equal comparison cycle (graphical LD)

suite id g_stop_eq
domain motor_control
language LD-graphical
difficulty easy
validation status candidate
origin plc-ld-dataset
license GPL-3.0

PLC-LD-dataset, github.com/UniboSecurityResearch/PLC-LD-dataset (Iacobelli et al., ICPS 2024, doi:10.1109/ICPS59941.2024.10639995); legitimate/lstop_eq.xml

What is proved

From benchmarks/motor_control/g_stop_eq/props.yaml. What each kind claims, and what it becomes on either route, is on The properties we prove.

id kind claim requirement
P1 invariant !(STOP && CYCLE_ON) STOP input must force the cycle off (safety interlock).

Variants

file expected verdict violates method
lstop_eq.xml SAFE none expert

Files

file what it is size sha256
NOTES.md notes 0.2 KB b566db2beb36
benchmark.yml benchmark metadata 0.7 KB d2af40286749
lstop_eq.xml ladder program, PLCopen XML 20.2 KB d94f8a9adcdd
props.yaml property file 0.2 KB 2cfc67d17b11

Structured text, derived

Read off the ladder graph by runner/ld_to_st.py: every rung's contacts and coils rewritten as IEC 61131-3 assignments, in the same series/parallel logic the PLCopen XML encodes. This is a reading aid, not a second source of expected verdicts; ESBMC verifies the ladder program shown above, never this rendering.

PROGRAM program0
VAR_INPUT
    TLB2 : INT;
    TLB1 : INT;
    STOP : BOOL;
    START : BOOL;
    IN1 : INT;
    VALUE : INT;
END_VAR

VAR_OUTPUT
    MV1 : BOOL;
    MV2 : BOOL;
    CYCLE_ON : BOOL;
END_VAR

VAR
    valves_handler0 : valves_handler;
    stop_cycle0 : stop_cycle;
END_VAR


valves_handler0(EN:=CYCLE_ON, IN1:=VALUE, IN_TLB1:=TLB1, IN_TLB2:=TLB2);
stop_cycle0(EN:=NOT CYCLE_ON);
CYCLE_ON := ((CYCLE_ON OR (IN1 = 1)) AND NOT STOP);
MV1 := valves_handler0.OUT_MV1;  (* 2 writers to MV1: scan order decides which value survives *)
MV2 := valves_handler0.OUT_MV2;  (* 2 writers to MV2: scan order decides which value survives *)
MV1 := stop_cycle0.OUT_MV1;  (* 2 writers to MV1: scan order decides which value survives *)
MV2 := stop_cycle0.OUT_MV2;  (* 2 writers to MV2: scan order decides which value survives *)

END_PROGRAM

Recorded runs

A task can carry two routes. ld is ESBMC's ladder front end reading the program directly. via C is the same solver reached through Beremiz and MatIEC, which is the only route that reaches ST, IL, FBD and SFC; see How ESBMC-PLC works.

  • g_stop_eq__lstop_eq (props.yaml, expected SAFE): v8.4 SAFE